This standard describes polyamide (Nylon-II-based) coating systems for
interior and exterior of steel pipe, connections, fittings, and special sections that are
used in water-handling equipment that is installed aboveground, belowground, or
underwater. Polyamide coating systems are thermoplastic and are ordinarily applied
in a shop or manufacturing facility.
1.1.1 M/n/mum pipe diameter. The minimum pipe diameter for application of the polyamide coating system to the interior of a pipe shall be the diameter that permits effective inspection and repair. For joints of pipe, this minimum
diameter is ordinarily 24 in. (600mm). For pipe diameters less than 24 in. (600 mm), the coating manufacturer shall be consulted regarding methods of
inspection and repair.